A relay and a contactor both open and close a circuit with a coil. They are not interchangeable once the load is a motor, a heater, or a lamp bank. Tradinor treats this as a buying decision: write the load, the coil, and the expected life on the RFQ, then let the datasheet pick the frame.
What actually changes the quote
The contact rating is a current at a voltage and a utilization category, not a single ampere number. AC-3 and AC-1 are different jobs. A device that is fine on a resistive heater can weld on a motor start. Inductive DC loads need a contact material and a magnet blowout that an AC-only part may not have. Write the load type in words.
Coil power decides the power supply and the cabinet heat. A contactor coil can draw several watts continuously, and the inrush is higher still. Put the coil voltage, AC or DC, and the control-supply tolerance on the drawing. If the coil is driven by a transistor, say so, because leakage can hold a sensitive relay in.
- Load: motor, heater, lamp, or signal, with voltage and full-load current.
- Utilization category the maker must meet, copied from the IEC table you design to.
- Coil voltage, AC or DC, and the dropout you can tolerate.
- Mechanical life and electrical life you actually need, in operations.
- Auxiliary contacts: quantity, NO or NC, and whether they must follow the power poles.
Ratings to copy from the datasheet
| Line on the RFQ | What to ask for | Why it moves the price |
|---|---|---|
| Contact category | AC-1, AC-3, DC-1, or DC-13, with current | A higher category is a larger frame |
| Coil | Rated voltage and operating limits | The wrong coil is a field failure, not a discount |
| Auxiliary | Number and type, mirrored if safety requires it | Added contacts change the cat. no. |
| Endurance | Electrical operations at your load | A short life is a cheaper contact alloy |
Incoming check
Confirm the coil marking and the contact diagram against the drawing before the part goes into the bin. A 24 V AC coil and a 24 V DC coil share a similar number and fail differently. Operate the sample on the real control supply, not on a stiff bench source, and listen for chatter at the low end of the tolerance. Do not invent a cycle-life test the datasheet already states; record the datasheet figure and the load you will actually switch.
What to lock on the order
On the purchase order, name the series and the coil code separately from the contact configuration. Factories substitute a same-looking frame with a different coil because the holder fits the rail. Write the control voltage next to the load current so the two cannot be split across lines. If the contactor must drop out when a safety circuit opens, say whether you need a mirror contact and name the standard your panel builder already designs to. Do not leave that as a note in email. Ask for the wiring diagram that shows which auxiliary follows the power poles, and attach it to the approved sample. A coil suppressor, if you need one, is a diode or an RC module rated for that coil. The wrong suppressor slows dropout. Specify it or state that the PLC output already includes suppression.
Questions buyers actually ask
Is a contactor just a large relay?
A contactor is built to switch motor and heater loads, with defined utilization categories. A signal relay is built for low energy. The name on the label does not replace the category.
What coil voltage should the drawing show?
The coil voltage and whether it is AC or DC, plus the allowed range. A 24 V DC coil on a supply that sags to 18 V will drop out.
Do I need an auxiliary contact?
Ask for it when a PLC input must see the contactor state. Do not assume the power poles can be used as a dry signal.